Torque connection tube. It uses a fixed-torque bolt (shear head) instead of the traditional hydraulic crimping. During installation, only an ordinary wrench is needed. When the bolt reaches the set torque, it will automatically break off, ensuring the contact pressure is just right. No large hydraulic pliers are required. It can be operated with a socket wrench alone, making it particularly suitable for narrow spaces or emergency repairs in the field.
It is mainly used for the connection of conductors in medium and high voltage cables, especially in the copper-aluminum transition scenarios. It is widely used in power engineering and distribution networks for the straight connection of copper conductors, aluminum conductors and aluminum alloy conductors, as well as for the copper-aluminum transition connection.
| Model | Conductor range | D1 | D2 | L1 | L2 | Bolt quantity | Bolt size |
| AMB10/35 | 10-35 | 19 | 8.5 | 45 | 20 | 2 | 13 |
| AMB25-95 | 25-95 | 24 | 12.8 | 65 | 30 | 2 | 13 |
| AMB35/150 | 35-150 | 28 | 15.8 | 80 | 35 | 2 | 17 |
| AMB95/240 | 95-240 | 33 | 20 | 125 | 60 | 4 | 19 |
| AMB120/300 | 120-300 | 37 | 24 | 140 | 65 | 4 | 20 |
| AMB185/400 | 185-400 | 42 | 25.5 | 170 | 80 | 6 | 22 |
| AMB500/630 | 500-630 | 50 | 33 | 200 | 95 | 6 | 27 |
For more detailed information about our products, please feel free to contact us for a quote.
We offer customized solutions specifically built to meet your exact specifications, environment and performance goals.
© 2025 ZHEJIANG LANGDAO ELECTRIC CO., LTD All Rights Reserved