LDEC offers an economical means of sealing the end of power cablewith a completely watertight seal. The internal surface of the end caphas a layer of spiral coated hot melt adhesive, which retains its lexibleproperties after recovery.LDEC is recommended for application both inopen air and on underground power distribution cables with PC. Lead orXLPE sheaths.
| Property | Test method | Typical data |
| Operating temperature (℃) | IEC 216 | -55 to +10 |
| Tensile strength (Mpa) | ASTM D 638 | ≥14 |
| Elongation at break (%) | ASTM D 638 | 400 |
| Density (g/cm3) | ASTM D 792 | 1.05 |
| Elongation at break after aging (%) | 150℃/168hrs | 300 |
| Dielectric strength (kV/mm) | IEC 243 | 15 |
| Volume resistance (Ω.cm) | IEC 93 | >1014 |
| Normal size (mm) | AS supplied(mm) | After recovered(mm) | Cable diameter (mm) | |||
| D(Min) | D(Max.) | A(10%) | L(10%) | Dw(5%) | ||
| LDEC–12/4 | 12 | 4 | 15 | 40 | 2.2 | 4–10 |
| LDEC–14/5 | 14 | 5 | 18 | 45 | 2.2 | 5–12 |
| LDEC–20/6 | 20 | 6 | 25 | 55 | 2.8 | 6–16 |
| LDEC–25/8.5 | 25 | 8.5 | 30 | 68 | 2.8 | 10–20 |
| LDEC–35/16 | 35 | 16 | 35 | 83 | 3.3 | 17–30 |
| LDEC–40/15 | 40 | 15 | 40 | 83 | 3.3 | 18–32 |
| LDEC–55/26 | 55 | 26 | 50 | 103 | 3.5 | 28–48 |
| LDEC–75/36 | 75 | 36 | 55 | 120 | 4 | 45–68 |
| LDEC–100/52 | 100 | 52 | 70 | 140 | 4 | 55–90 |
| LDEC–120/60 | 120 | 60 | 70 | 150 | 4 | 65–110 |
| LDEC–160/82 | 160 | 82 | 70 | 150 | 4 | 90–150 |